Inrush current limiter EBN-OS

For POWERTRONIC ECGs

Picture

POWERTRONIC ECGs in combination with EBN-OS

POWERTRONIC ECGs come with an electronic power factor correction (PFC), which causes a high inrush current. If several PT ECGs are switched on at the same time, the inrush current can be so high that the automatic circuit breaker will trigger. Therefore, the number of ECGs per automatic circuit breaker is limited.

The inrush current limiter allows to connect more ECGs to one automatic circuit breaker.

EBN-OS is for POWERTRONIC only.

  • Up to 2.5 times more ECGs per circuit breaker
  • Limitation of capacitive inrush currents
  • Maximum continuous rate: 16 A
  • Inrush current limitation time: 70 ms
  • Dimensions in mm: 18 x 88 (45) x 58
  • For hat rail mounting